Minilec Phase Failure Relays D2 VMR2
Overview
- Suitable for 3 Ph-4W system
- Microcontroller design
- Absolute values of UV/OV settings
- Phase Failure, Unbalance
- Phase Sequence, Under voltage
- Over Voltage, Auto/Manual reset
- Adjustable settings for Unbalance
- UV/OV and trip delays
- 2 CO output relay
- Neutral Fail Protection
- Technical Specification
Supply Voltage
- System100-120 / 220-240 / 380-440V AC -25%+20%, 48-63 Hz
- AuxillaryBuilt In (from 3 Phase)
Output Contacts
Trip Setting(Volts)
- Phase SequenceYes
- Phase Unbalance4 % - 20 % [Variable]
- Under VoltageFor 380-440V AC
For 220-240V AC
For 100-120V AC165-245V AC [Variable]
95-135V AC [Variable]
45-65V AC [Variable] - Over VoltageFor 380-440V AC
For 220-240V AC
For 100-120V AC230-310V AC [Variable]
130-170V AC [Variable]
60-80V AC [Variable]
Trip Time Delay
- On Phase FailureInstant
- On UV/OV1 To 10 Sec [Variable)
- NF2 Sec ± 1.5 Sec. (Fixed)
Resetting Mode
- Resetting ModeAuto/ External Manual Reset (External NC Push Buttons)
Weight
Dimensions (mm)
- Overall (L x W x D)76 X 56.5 X 117.5
- Mounting (L x W)67 x 46 / 35 mm rail Mounting
Note:
- Wherever not specified Contact Rating : 5A @ 230 V AC (resistive)
Timing/ Relay logic Diagram
Electrical Connection Diagram
Applications
Suitable for monitoring 3 Ph. System supply from MAINS & used by motor load:
- AC & R Chiller compressor motors
- AHU Fan /Pump Motors
- Machinery using multiple small motors
- MAIN powers supply distribution panel board
- DG Set application
- UPS
- Submersible Pumps
- Hoist & Crane