Overview
- Microcontroller design
- SMD Technology
- Phase Failure, Unbalance
- Phase Sequence, Under voltage
- Over Voltage, Auto reset
- Neutral Voltage
- Adjustable UV/OV settings
- 2 CO output relay
- System supply voltage 415 VAC
Supply Voltage
- System415 VAC ± 20%, 3Phase, 4Wire System
- AuxillaryIn Built
Frequency
Output Contacts
Output Contacts Rating
- Output Contacts Rating5 AMP1 240 VAC (Resistive)
Unbalance Trip Setting
- Unbalance Trip Setting94 V ± 6V ph - ph (Fixed)
Trip Setting
- Under Voltage75% to 95% of 415 VAC
- Over Voltage105% to 125% of 415 VAC
Power on Delay
- Power on Delay5 Sec. ± 1 Sec. (Fixed)
Trip Time Delay
- *UB/ SP/UV/OV5 Sec. ± 1 Sec. (Fixed)
- *RPInstant
- *Neutral FailLess than 2 Sec.
Set Accuracy
- *UB/ SP/UV/OV± 2 % of Set Value
Resetting Mode
Reset Gap
- *Unbalance reset gap14 V ± 4 V
- *UV & OV reset gap3% ± 1% of set value
Enclosures
- EnclosuresS2 Series, ABS / PC-ABS
Weight
Dimensions (mm)
- Overall (L x W x D)90 x 35 x 60
- Mounting (L x W)35 mm rail Mounting
Connection Diagrams
Timing/ Relay logic Diagram

Electrical Connection Diagram

Applications
Suitable for monitoring 3 Ph. System supply from MAINS & used by motor load :